Home › Guides › Florida restaurant fire extinguishers
Florida restaurant fire extinguishers: Class K and service
- Pick what you need and give your kitchen's ZIP code.
- Each service goes to the number of local companies you choose, from one to five. We check licenses where the law requires one and email you their names.
- You talk with them and decide. You hire and pay the company directly.
Facts checked 2026-11-02.

A commercial kitchen needs a Class K extinguisher near the cooking line for grease fires, plus the usual extinguishers for the rest of the building. You check them every month. A licensed Florida fire equipment company services them every year and tags each one.
Which extinguishers a kitchen needs
A Class K extinguisher is made for cooking oil and grease fires. DBPR's plan packet says Class K extinguishers and automatic hood suppression are required when grease-laden vapors or smoke are produced.
The Florida Building Code puts portable extinguishers within 30 feet of commercial cooking equipment. The extinguisher has to be a type approved for cooking grease fires and compatible with the agent in the hood suppression system.
Florida's Fire Prevention Code adopts NFPA 10 (2018). Ask your fire marshal how many extinguishers, and which types, the rest of your building needs.
A hand-held extinguisher does not replace the hood system. See fire suppression systems.
The monthly check
NFPA 10 asks the building owner to check extinguishers about every 30 days. Guidance from the Minnesota Department of Health, based on a 2010 edition of NFPA 10, says trained staff can do it. It is a visual check. Your fire equipment company or fire marshal can tell you what to look at and what record to keep.
A local company can take it from here. One form, free for restaurants.
Get connectedYearly service
Rule 69A-21 says maintenance of extinguishers follows NFPA 10 and the maker's manual, and it is done at least once a year. After each service the dealer:
- Replaces the tamper seal. Seals are replaced every year under the rule.
- Attaches a tag with the servicer's name and permit number.
- Gives you an invoice that shows the business name, address and license number, and the serial number and service done for each extinguisher.
Check the invoice against the extinguishers on the wall. If the serial numbers do not match, ask the company.
Six-year and 12-year work
Some extinguishers need more than the yearly service. The Minnesota guide, based on NFPA 10 (2010), lists these intervals:
| Work | Interval | Applies to |
|---|---|---|
| Emptying and examining inside | Every 6 years | Stored-pressure dry chemical extinguishers |
| Internal examination | Every 5 years | CO2 and wet chemical (Class K) extinguishers |
| Hydrostatic test | Every 5 years | Water, CO2, wet chemical and stainless steel dry chemical |
| Hydrostatic test | Every 12 years | Other dry chemical extinguishers |
| Removal from service | 12 years after manufacture | Non-rechargeable extinguishers |
Florida adopts a newer edition of NFPA 10, so confirm the intervals with your fire equipment company. Florida's rule 69A-21 also calls for a six-year maintenance record decal on certain stored-pressure extinguishers. The dealer applies it when the work is done.
Who is allowed to service them
Florida law requires a State Fire Marshal license for any business that services, recharges, tests, inspects, installs or hydrotests fire extinguishers. Each location has its own license, and each technician also needs a permit.
| License | What it covers |
|---|---|
| Class A | All extinguisher work, including hydrostatic testing of all types |
| Class B | The same, but hydrostatic testing leaves out CO2 |
| Class C | Leaves out CO2 recharge and CO2 hydrostatic testing |
| Class D | Pre-engineered systems, which include restaurant hood systems |
Ask for the license number and the technician's permit number. Florida law makes it a crime to do or advertise contracting work without the right license. See fire suppression systems for how to check a company.
Fire chiefs, fire inspectors, fire marshals and insurance inspectors can inspect extinguishers without this license. The license applies to the people who service them.
For yearly extinguisher service, fill in the form and we'll pass your request to one licensed local fire equipment company.
Questions
Do restaurants need a Class K extinguisher?
DBPR says Class K extinguishers are required where grease-laden vapors or smoke are produced. The Florida Building Code puts extinguishers within 30 feet of cooking equipment.
How often must fire extinguishers be serviced in a Florida restaurant?
Fire extinguishers need service at least once a year, with a tag showing the servicer's name and permit number. Some types also need 5-year, 6-year or 12-year work.
Can my kitchen staff service the fire extinguishers?
Staff can do the monthly check. Servicing, recharging and hydrostatic testing need a business licensed by the State Fire Marshal and a permitted technician.
What should a fire extinguisher service invoice show?
A fire extinguisher service invoice shows the business name, address and license number, and the serial number and service done for each extinguisher.
Sources
- Florida Statutes 633.304, fire equipment licenses
- Chapter 69A-21, Florida Administrative Code (State Fire Marshal PDF)
- Rule 69A-3.012, adopted NFPA editions
- DBPR plan review packet (HR-7030)
- Florida Building Code, Building, chapter 9 (UpCodes copy)
- Minnesota Department of Health, portable fire extinguishers
- State Fire Marshal, regulatory licensing
- Florida Statutes 489.127, unlicensed contracting